CEA Practice Questions (2026) — Free Sample Questions with Answers

15 free CEA questions from our 150-question bank, grouped by content domain. Each answer explains why the right option is right — and why every wrong option is wrong.

0 of 15 answered — answer a question to check it Take a full CEA practice test

Developing an Energy Audit Strategy & Plan

Question 1

A property manager wants a low-cost first look at a 60,000 sq ft office building: a review of two years of utility bills, a brief walk-through of the building, and a list of no-cost/low-cost measures plus potential capital measures worth studying further. Under ASHRAE Standard 211, which audit level matches this scope?

Show answer & explanation

Answer: C

Preliminary energy-use analysis only: The preliminary energy-use analysis reviews bills and benchmarks the building but includes no site visit; this scope adds a walk-through.

Level 2 energy survey and analysis: Level 2 requires a detailed survey, an end-use breakdown and savings and cost estimates for each measure — more than the manager asked for.

Level 1 walk-through: Correct. BoK 104/113 — ASHRAE 211 Level 1 adds a brief site walk-through to the bill analysis and identifies no-cost/low-cost measures and capital measures that merit further study.

Level 3 detailed analysis of capital-intensive modifications: Level 3 is investment-grade analysis of capital projects with extensive data collection; far beyond a low-cost first look.

ASHRAE 211 levels build on one another: preliminary analysis (bills only) → Level 1 (adds walk-through, low-cost measures) → Level 2 (detailed survey, end-use breakdown, measure costs and savings) → Level 3 (detailed analysis of capital-intensive measures).

Energy Use Analysis

Question 2

The chart plots monthly average daily gas use against average outdoor temperature for a school whose thermostats are held at 72°F. Below the change point, daily therms = 520 − 8 × T (°F); above it, use is flat at a 40 therm/day base load. What is the building's heating balance point temperature?

Average daily gas use vs. outdoor temperature05010015020025030035040020304050607080Average outdoor temperature (°F)Gas use (therms/day)
Show answer & explanation

Answer: A

  1. At the balance point, heating gas use falls to the base load: 520 − 8T = 40 therms/day
  2. 8T = 520 − 40 = 480
  3. T = 480 ÷ 8 = 60°F

60°F: Correct. BoK 209 — the heating line meets the 40 therm/day base load where 520 − 8T = 40, so T = 480 ÷ 8 = 60°F.

65°F: Solves 520 − 8T = 0 (zero gas use) and ignores the 40 therm/day base load; it also matches the conventional 65°F degree-day base, which is not this building's balance point.

70°F: Adds the base load instead of subtracting it: (520 + 40) ÷ 8 = 70°F.

72°F: Equates the balance point with the thermostat set point; internal and solar gains make the balance point lower than the set point.

The balance point is the outdoor temperature at which weather-dependent use reaches zero (the change point to base load); it sits below the set point because internal gains supply heat.

Data Collection & Analysis

Question 3

A regression of baseline-year bills gives monthly kWh = 42,000 + 310 × CDD. After a retrofit, a month with 250 CDD shows a metered use of 101,500 kWh. Calculate the avoided energy for that month.

Show answer & explanation

Answer: A

  1. Adjusted baseline = 42,000 + 310 kWh/CDD × 250 CDD = 42,000 + 77,500 = 119,500 kWh
  2. Avoided energy = 119,500 kWh − 101,500 kWh = 18,000 kWh

18,000 kWh: Correct. BoK 307 — adjusted baseline = 42,000 + 310 × 250 = 119,500 kWh; 119,500 − 101,500 = 18,000 kWh.

24,000 kWh: Leaves out the 42,000 kWh intercept (base load) and compares 77,500 kWh with the metered use.

42,000 kWh: Reports the intercept (weather-independent base load) as the savings.

119,500 kWh: Reports the weather-adjusted baseline itself instead of the difference from metered use.

Avoided energy = baseline model evaluated at reporting-period conditions − metered use; keep both the intercept and the slope term.

Question 4

A lighting retrofit in an office saves 90,000 kWh/yr. Half of these savings occur during the cooling season, and all of that lighting heat had been removed by a chiller plant averaging 0.80 kW/ton. Calculate the additional cooling energy saved.

Show answer & explanation

Answer: A

  1. Cooling-season lighting savings = 0.5 × 90,000 kWh = 45,000 kWh
  2. Heat no longer added = 45,000 kWh × 3,412 Btu/kWh = 153,540,000 Btu
  3. Avoided cooling = 153,540,000 Btu ÷ 12,000 Btu/ton-h = 12,795 ton-h
  4. Chiller energy saved = 12,795 ton-h × 0.80 kW/ton = 10,236 kWh/yr

10,236 kWh/yr: Correct. BoK 306 — 45,000 kWh × 3,412 Btu/kWh ÷ 12,000 Btu/ton-h = 12,795 ton-h; × 0.80 kW/ton = 10,236 kWh/yr.

12,795 kWh/yr: Stops at ton-hours of avoided cooling and reports them as kWh without applying 0.80 kW/ton.

15,994 kWh/yr: Divides ton-hours by 0.80 kW/ton instead of multiplying (ratio inverted).

20,472 kWh/yr: Applies the cooling effect to all 90,000 kWh instead of the half that occurs in the cooling season.

Lighting savings in conditioned space cut cooling load: kWh × 3,412 ÷ 12,000 gives ton-hours, times kW/ton gives the chiller kWh saved.

Economic Analysis

Question 5

Chiller A costs $200,000 installed and $40,000/yr to operate. Chiller B costs $260,000 installed and $30,000/yr to operate. Both last 15 years with equal maintenance and no salvage value. At a 6% discount rate, by how much is Chiller B's life-cycle cost lower than Chiller A's?

Show answer & explanation

Answer: A

  1. P/A (6%, 15 yr) = (1 − 1.06⁻¹⁵) ÷ 0.06 = 9.712
  2. LCC A = $200,000 + $40,000 × 9.712 = $588,490
  3. LCC B = $260,000 + $30,000 × 9.712 = $551,370
  4. Difference = $588,490 − $551,370 = $37,120 ≈ $37,100 in favor of Chiller B

$37,100: Correct. BoK 403 — PV of the $10,000/yr operating difference = $10,000 × (1 − 1.06⁻¹⁵) ÷ 0.06 = $97,120; minus the $60,000 extra first cost = $37,100 lower LCC for B.

$60,000: Reports the first-cost difference, which actually favors Chiller A, and ignores operating costs.

$90,000: Uses undiscounted operating savings ($10,000 × 15 = $150,000) minus the $60,000 first-cost premium.

$97,100: Counts the present value of operating savings but forgets to subtract Chiller B's $60,000 higher first cost.

LCC = first cost + present value of recurring costs over the study period; the lower-LCC option is preferred even when its first cost is higher.

Lighting Systems

Question 6

A school replaces 200 fluorescent fixtures (62 W input each) with LED fixtures (30 W input each). The lights operate 4,000 h/yr and are on at the monthly peak every month. Electricity costs $0.11/kWh plus $14/kW-month. The retrofit costs $18,000. Ignoring HVAC interactive effects, calculate the simple payback.

Show answer & explanation

Answer: A

  1. kW saved = 200 × (62 − 30) W ÷ 1,000 = 6.4 kW
  2. kWh saved = 6.4 kW × 4,000 h/yr = 25,600 kWh/yr
  3. Energy savings = 25,600 × $0.11 = $2,816/yr
  4. Demand savings = 6.4 kW × $14/kW-month × 12 months = $1,075/yr
  5. Total = $3,891/yr
  6. SPP = $18,000 ÷ $3,891/yr = 4.6 years

4.6 years: Correct. BoK 511 — 6.4 kW saved gives $2,816/yr energy + $1,075/yr demand = $3,891/yr; $18,000 ÷ $3,891 = 4.6 years.

6.2 years: Applies the $14/kW demand charge for one month only instead of 12 months.

6.4 years: Uses energy savings only and omits the $14/kW-month demand savings.

16.7 years: Uses demand savings only and omits the 25,600 kWh/yr energy savings.

Lighting retrofit savings = ΔkW × hours × energy rate + ΔkW × demand rate × months on peak; payback = cost ÷ total annual savings.

Heating, Ventilation & Air Conditioning Systems

Question 7

A 20,000-cfm supply fan runs 5,000 h/yr. Loaded filters add 0.5 in. w.g. of pressure drop compared with clean filters. Fan efficiency is 65% and motor efficiency is 90%. Using bhp = cfm × in. w.g. ÷ (6,356 × fan efficiency), determine the added annual electricity use caused by the loaded filters.

Show answer & explanation

Answer: D

  1. bhp = 20,000 cfm × 0.5 in. w.g. ÷ (6,356 × 0.65) = 10,000 ÷ 4,131.4 = 2.42 hp
  2. Input kW = 2.42 hp × 0.746 kW/hp ÷ 0.90 = 2.006 kW
  3. Added energy = 2.006 kW × 5,000 h = 10,032 kWh/yr

6,521 kWh: Omits the 65% fan efficiency, giving air horsepower instead of brake horsepower.

8,126 kWh: Multiplies by the 90% motor efficiency instead of dividing by it.

9,028 kWh: Converts brake hp to kW but omits the motor efficiency, giving motor output instead of electrical input.

10,032 kWh: Correct. BoK 609 — bhp = 20,000 × 0.5 ÷ (6,356 × 0.65) = 2.42 hp; input = 2.42 × 0.746 ÷ 0.90 = 2.006 kW × 5,000 h = 10,032 kWh.

Added fan power = cfm × Δ(in. w.g.) ÷ (6,356 × fan eff) in bhp, then × 0.746 ÷ motor eff for kW input; change filters on pressure drop, not on a calendar alone.

Question 8

An office building plans to replace its 300-ton chiller with a high-efficiency unit. The chiller runs at full load during the monthly billing peak in each of the six cooling months. Using the data in the table, calculate the simple payback of the replacement.

Chiller replacement data
ItemValue
Existing chiller efficiency0.90 kW/ton
Proposed chiller efficiency0.55 kW/ton
Average cooling load210 tons
Annual operating hours2,000 h
Cooling load at billing peak300 tons (6 months)
Energy charge$0.11/kWh
Demand charge$14/kW-month
Installed cost$150,000
Show answer & explanation

Answer: C

  1. Δ efficiency = 0.90 − 0.55 = 0.35 kW/ton
  2. Energy saved = 210 tons × 0.35 kW/ton × 2,000 h = 147,000 kWh/yr
  3. Energy savings = 147,000 kWh × $0.11/kWh = $16,170/yr
  4. Demand reduction = 300 tons × 0.35 kW/ton = 105 kW
  5. Demand savings = 105 kW × $14/kW-month × 6 months = $8,820/yr
  6. Total = $16,170 + $8,820 = $24,990/yr
  7. SPP = $150,000 ÷ $24,990/yr = 6.00 years

4.44 yr: Applies the $14/kW demand savings for 12 months instead of the six cooling months.

4.70 yr: Computes energy savings at the 300-ton full load for all 2,000 hours instead of the 210-ton average load.

6.00 yr: Correct. BoK 612 — energy savings $16,170 plus demand savings $8,820 = $24,990/yr; $150,000 ÷ $24,990 = 6.00 years.

9.28 yr: Counts only the energy savings and omits the demand-charge savings.

Chiller savings = tons × Δ(kW/ton) × hours for energy, plus peak tons × Δ(kW/ton) × $/kW-month × months for demand; payback = cost ÷ total annual savings.

Domestic Hot Water Systems

Question 9

A fitness center averages 250 showers/day, 8 minutes each, 360 days/yr. Replacing 2.5 gpm showerheads with 1.5 gpm models is proposed. Treat all shower water as heated from 50°F to 105°F by a gas water heater that is 80% efficient, with gas at $0.90/therm. Determine the annual gas cost savings.

Show answer & explanation

Answer: C

  1. Flow reduction = 2.5 − 1.5 = 1.0 gpm
  2. Water saved = 250 showers/day × 8 min × 1.0 gpm × 360 days = 720,000 gal/yr
  3. Heat saved = 8.34 × 720,000 gal × (105 − 50)°F = 330,264,000 Btu/yr
  4. Fuel saved = 330,264,000 ÷ 0.80 = 412,830,000 Btu = 4,128 therms/yr
  5. Cost savings = 4,128 therms × $0.90 = $3,715/yr

$2,378: Multiplies the heat saved by the 80% efficiency instead of dividing by it.

$2,972: Leaves out the 80% water heater efficiency, so it counts only the heat delivered to the water.

$3,715: Correct. BoK 705/707 — 720,000 gal/yr saved × 8.34 × 55°F ÷ 0.80 = 4,128 therms × $0.90 = $3,715/yr.

$5,573: Uses the new 1.5 gpm flow instead of the 1.0 gpm reduction, which values the water still used rather than the water saved.

Hot-water savings from low-flow fixtures = gallons saved × 8.34 × ΔT ÷ heater efficiency, then convert to fuel units and cost.

Motors & Drives & Compressed Air Systems

Question 10

An air-cooled rotary screw compressor at a warehouse draws 90 kW input and is fully loaded. About 80% of its input energy can be recovered as heat and ducted into the space for 3,000 h/yr of heating. It would displace a gas furnace with 80% efficiency; gas costs $1.00/therm. Determine the annual savings.

Show answer & explanation

Answer: C

  1. Recoverable heat = 90 kW × 0.80 × 3,412 Btu/kWh = 245,664 Btu/h
  2. Annual heat delivered = 245,664 Btu/h × 3,000 h = 736,992,000 Btu
  3. Gas input avoided = 736,992,000 Btu ÷ 0.80 = 921,240,000 Btu
  4. Therms avoided = 921,240,000 ÷ 100,000 = 9,212 therms
  5. Savings = 9,212 therms × $1.00/therm = $9,212/yr

$5,896: Multiplies by the furnace efficiency instead of dividing, which understates the fuel avoided.

$7,370: Leaves out the furnace efficiency; each Btu recovered displaces 1 ÷ 0.80 Btu of gas input.

$9,212: Correct. BoK 811 — 90 kW × 0.80 × 3,412 = 245,664 Btu/h; × 3,000 h ÷ 0.80 ÷ 100,000 = 9,212 therms × $1.00 = $9,212/yr.

$11,516: Treats all 90 kW of input as recoverable heat, ignoring the 80% recovery fraction.

Heat recovered from a compressor offsets fuel input = recovered Btu ÷ the displaced heater's efficiency.

Question 11

A chilled-water distribution pump runs at full speed for 6,000 h/yr, drawing 30 kW. A VFD will let it follow the load profile shown. Assume ideal affinity laws, no static head and no drive losses. Determine the annual energy savings.

Proposed VFD operating profile
Pump speedHours per year
100%2,000
80%2,000
60%2,000
Show answer & explanation

Answer: C

  1. Baseline = 30 kW × 6,000 h = 180,000 kWh/yr
  2. 100%: 30 kW × 1.000 × 2,000 h = 60,000 kWh
  3. 80%: 30 kW × 0.8³ = 30 × 0.512 = 15.36 kW × 2,000 h = 30,720 kWh
  4. 60%: 30 kW × 0.6³ = 30 × 0.216 = 6.48 kW × 2,000 h = 12,960 kWh
  5. VFD total = 60,000 + 30,720 + 12,960 = 103,680 kWh/yr
  6. Savings = 180,000 − 103,680 = 76,320 kWh/yr

36,000 kWh: Treats power as proportional to speed (linear), which is the relation for flow, not power.

60,000 kWh: Uses the square of speed; that relation applies to head or pressure, not power.

76,320 kWh: Correct. BoK 806 — power ∝ speed³: 30 kW × (2,000 × 1 + 2,000 × 0.512 + 2,000 × 0.216) = 103,680 kWh; 180,000 − 103,680 = 76,320 kWh saved.

103,680 kWh: This is the energy used with the VFD, not the energy saved.

Affinity laws: flow ∝ speed, head ∝ speed², power ∝ speed³; weight each speed by its hours and compare with the baseline.

Building Envelope

Question 12

A 10,000 ft² roof has a total R-value of R-10. Adding R-20 of insulation is proposed. Monthly heating degree days (65°F base) for the site are shown. The building is heated by an 80% efficient gas furnace, with gas at $1.10/therm. Determine the annual heating cost savings.

Monthly heating degree days (65°F base)020040060080010001200JanFebMarAprMayJunJulAugSepOctNovDecMonthHDD
Show answer & explanation

Answer: D

  1. Annual HDD = 1,000 + 850 + 700 + 400 + 150 + 0 + 0 + 0 + 100 + 400 + 600 + 800 = 5,000 °F·day
  2. U existing = 1 ÷ 10 = 0.100; U new = 1 ÷ (10 + 20) = 0.0333 Btu/h·ft²·°F
  3. Heat saved = (0.100 − 0.0333) × 10,000 ft² × 5,000 × 24 h/day = 80,000,000 Btu/yr
  4. Fuel saved = 80,000,000 ÷ 0.80 = 100,000,000 Btu = 1,000 therms
  5. Savings = 1,000 therms × $1.10 = $1,100/yr

$46: Leaves out the 24 h/day factor that converts degree days to degree-hours.

$825: Takes the new U as 1 ÷ 20 (the added insulation alone) instead of 1 ÷ 30 for the whole assembly.

$880: Leaves out the 80% furnace efficiency, so it counts only the heat saved at the roof.

$1,100: Correct. BoK 909 — annual HDD = 5,000; ΔU = 0.100 − 0.0333 = 0.0667; 0.0667 × 10,000 × 5,000 × 24 = 80 MMBtu ÷ 0.80 = 1,000 therms × $1.10 = $1,100/yr.

Annual conduction heat loss = U × A × HDD × 24; to find savings, add R-values first, take U = 1/R, and divide by heating efficiency.

BAS, PAS and EMCS

Question 13

The trend log shows temperatures for a 10,000 cfm air handler at a library. Using the 10:00 readings, how much outdoor air is the unit delivering?

AHU-2 temperature trend4045505560657075806:007:008:009:0010:0011:0012:0013:0014:00Time of dayTemperature (°F)
Return air Mixed air Outdoor air
Show answer & explanation

Answer: B

  1. 10:00 readings: RAT = 74°F, MAT = 70.4°F, OAT = 56°F
  2. OA fraction = (RAT − MAT) ÷ (RAT − OAT) = (74 − 70.4) ÷ (74 − 56) = 3.6 ÷ 18 = 0.20
  3. OA flow = 0.20 × 10,000 cfm = 2,000 cfm

486 cfm: Divides (RAT − MAT) by the return temperature itself instead of by (RAT − OAT).

2,000 cfm: Correct. BoK 1005 — OA fraction = (RAT − MAT) ÷ (RAT − OAT) = (74 − 70.4) ÷ (74 − 56) = 3.6 ÷ 18 = 0.20; 0.20 × 10,000 = 2,000 cfm.

2,500 cfm: Divides by (MAT − OAT) instead of (RAT − OAT), which is the ratio of outdoor to return air, not the outdoor fraction.

8,000 cfm: This is the return-air flow; (MAT − OAT) ÷ (RAT − OAT) = 0.80 is the return fraction.

A mixed-air temperature balance gives OA fraction = (RAT − MAT) ÷ (RAT − OAT); a constant 20% with mild outdoor air suggests the economizer is stuck at minimum.

Alternative Generation & Storage

Question 14

A first-cut screening is done for a 500-kW CHP unit at a manufacturing plant. The recovered heat displaces fuel in an 80%-efficient boiler that burns the same gas. Using the table, determine the CHP unit's net annual operating savings.

CHP screening data
ItemValue
Net electric output500 kW
Operating hours7,000 h/yr
Gas input to CHP5.2 MMBtu/h
Useful heat recovered2.4 MMBtu/h
Displaced grid electricity price$0.12/kWh
Natural gas price$6.00/MMBtu
CHP O&M cost$0.02/kWh generated
Show answer & explanation

Answer: D

  1. Electricity = 500 kW × 7,000 h = 3,500,000 kWh; value = 3,500,000 × $0.12 = $420,000
  2. CHP fuel = 5.2 MMBtu/h × 7,000 h = 36,400 MMBtu × $6.00 = $218,400
  3. Boiler fuel displaced = 2.4 × 7,000 ÷ 0.80 = 21,000 MMBtu × $6.00 = $126,000
  4. O&M = 3,500,000 kWh × $0.02 = $70,000
  5. Net = $420,000 − $218,400 + $126,000 − $70,000 = $257,600/yr

$131,600: Leaves out the credit for recovered heat that displaces boiler fuel.

$212,240: Multiplies the recovered heat by the 80% boiler efficiency instead of dividing, undervaluing the heat credit.

$232,400: Credits recovered heat at face value without dividing by the 80% boiler efficiency.

$257,600: Correct. BoK 1106 — $420,000 power value − $218,400 CHP fuel + $126,000 boiler-fuel credit − $70,000 O&M = $257,600.

CHP net savings = displaced grid electricity + displaced boiler fuel (recovered heat ÷ boiler efficiency × fuel price) − CHP fuel − CHP O&M.

Transport

Question 15

A service truck uses 2,000 gal/yr of gasoline at 20.0 mpg. Removing an unused roof rack and fitting low-rolling-resistance tires raise its fuel economy to 21.0 mpg with the same annual mileage. At $3.50/gal, determine the annual fuel-cost savings.

Show answer & explanation

Answer: A

  1. Annual miles = 2,000 gal × 20.0 mpg = 40,000 mi
  2. New fuel use = 40,000 mi ÷ 21.0 mpg = 1,904.8 gal
  3. Fuel saved = 2,000 − 1,904.8 = 95.2 gal
  4. Savings = 95.2 gal × $3.50/gal = $333/yr

$333: Correct. BoK 1208 — miles = 2,000 × 20 = 40,000; new fuel = 40,000 ÷ 21 = 1,904.8 gal; saved 95.2 gal × $3.50 = $333/yr.

$350: Assumes a 5% mpg gain cuts fuel use by 5% (100 gal); fuel use falls by only 1 − 20/21 = 4.76%.

$368: Divides fuel use by 0.95 (2,000 ÷ 0.95 − 2,000 = 105 gal), applying the percentage the wrong way.

$6,667: Reports the new annual fuel cost (1,904.8 gal × $3.50) instead of the savings.

Fuel use varies with 1/mpg, so a percentage gain in mpg yields a smaller percentage cut in gallons; convert through miles, not by applying the mpg percentage to fuel.