Range, Approach, and the Weather: Reading a Cooling Tower
1The condenser at a steam plant needs a steady supply of cool water, and in many plants that water comes from a cooling tower. Warm water from the condenser is pumped to the top of the tower and allowed to fall through it while air moves past. A small part of the water evaporates, and evaporation draws heat out of the water that remains. The cooled water collects in a basin and returns to the condenser to pick up heat again.
2Towers move air in one of two ways. A natural-draft tower is the tall, curved concrete shell often seen from the highway. Warm, moist air inside the shell is lighter than the air outside, so it rises out of the top on its own, the way smoke rises up a chimney, and cooler air is drawn in near the bottom. A mechanical-draft tower is much shorter and uses large fans to push or pull the air. Fans give operators more control, but they use electric power and need regular maintenance.
3Two numbers describe how a tower is working. The range is the difference between the temperature of the hot water entering the tower and the temperature of the cold water leaving it. If water arrives at 105°F and leaves at 85°F, the range is 20 degrees. The range is set mostly by how much heat the condenser puts into the water. The approach is the difference between the cold-water temperature and the wet-bulb temperature of the outside air.
4The wet-bulb temperature is read from a thermometer whose bulb is wrapped in a wet cloth and kept in moving air. It is lower than the ordinary air temperature whenever the air is not saturated, that is, whenever the air could still hold more water vapor, because water evaporating from the cloth cools the bulb. The wet-bulb reading shows how much cooling by evaporation the air can still provide. A tower can bring its water close to the wet-bulb temperature, but never below it.
5These ideas explain why tower performance changes with the weather. On a dry day the wet-bulb temperature is low, and the tower can deliver cold water even when the air feels hot. On a humid day the wet-bulb temperature rises close to the air temperature, and the water leaving the tower is warmer. If the approach grows larger while the weather and load stay the same, operators look for a problem in the tower itself, such as clogged fill, a failed fan, or poor water spray.
What is the main purpose of paragraph 2?
Show answer & explanation
Answer: B
To explain why evaporation cools the water: Evaporation is explained in paragraph 1.
To compare the two ways that towers move air: Correct. Paragraph 2 opens "Towers move air in one of two ways" and then describes natural-draft and mechanical-draft towers.
To show that tall towers cool water best: Not stated: paragraph 2 never says which kind of tower cools better.
To describe how tower fans are maintained: True-but-partial: maintenance is mentioned in one phrase, not explained.
A topic sentence such as "Towers move air in one of two ways" usually announces the paragraph's purpose.