A water heater's temperature and pressure relief (TPR) valve discharge pipe has a ball valve installed partway along it, and the ball valve is closed. What is the BEST report statement?
Show answer & explanation
Answer: C
No defect; the valve allows servicing the TPR valve: Folk explanation; no valve is allowed in a TPR discharge line, whatever the reason.
Minor item; open the ball valve and leave it: Partial; opening it helps for now, but the valve can be closed again and must be removed.
Closed valve blocks relief; refer to a plumber: Correct. The discharge pipe must be full size and free of valves so the TPR valve can relieve dangerous pressure or temperature. A closed valve defeats it. Report it as a safety defect and refer to a plumber.
Pipe end too low; raise it to 18 in above the floor: Rule from another component; 18 in is the ignition-source elevation for garage appliances, and a TPR discharge should end within 6 in of the floor.
TPR discharge piping must be full size, unvalved, untrapped and end near the floor or at another approved point.